Universal Voltage GMT Fuse Panels, 20A
SPECIFICATIONS
| Nominal voltage | ±24 to -48 VDC |
| Input rating | 100A or 60A per bus, based on configuration |
| Maximum input interrupt device | 125A
GMT20 Panel: 75A |
| Maximum output protection device | 20A (15A) |
| Power dissipation (full load) | 12W per bus (10W for panel with
15A fuses)
|
| |
| Weight | 9 lbs. (4.08 kgs.) |
| Material | Cold-rolled steel |
| Color | White |
| Finish | Powder coat |
| Mounting | 19" or 23"
HPGMT20 and GMT10FA: 23" only |
| |
| Temperature | -5° to 55° C |
| Humidity | 0 to 90%,non-condensing |
| |
| Input terminals | Dual stud,1/4"on 5/8"centers for 100A input panels
GMT20 Panel: Barrel lug (screw-tight)
|
| Output terminals | Screw terminal,#6
GMT20 Panel: Screw terminal, #3 |
| Chassis ground | Dual stud,#10 on 5/8"centers |
| |
| Alarm indicators | Power, fuse, bay alarm |
| Alarm type | Form C |
| Alarm connector | 0.045" square pin |
| Relay contact ratings | 0.6A at 48 VDC;1A at 120 VAC |
| |
| Agency compliance | NEBS 3, UL, CUL |
| |
|