GMT Fuse Panels, 10A Fuse Max.
SPECIFICATIONS
| Nominal voltage | -24V to -48V |
| Input rating | Dual 20 panels: 20A per bus Dual 10 panel: 50A per bus |
| Maximum input interrupt device | Dual 20 panels: 20A per bus Dual 10 panel: 60A per bus |
| Maximum output protection device | Dual 20 panels: 10A Dual 10 panel: 15A |
| Power dissipation (full load) | 8W per bus |
| |
| Weight | 10 lbs. (4.54 kgs.) |
| Material | Cold-rolled steel |
| Finish | Gray or black, powder coat |
| Mounting | 19" or 23" |
| |
| Temperature | -5 to 55° C |
| Humidity | 0 to 90%, non-condensing |
| |
| Input terminals | Wire clamp |
| Output terminals | Dual 20 panels: Wire clamp
Dual 10 panel: Screw terminals |
| Chassis ground | #10 screw |
| |
| Alarm indicators | Power, fuse alarms
06020-01 also equipped with bay alarm |
| Alarm type | Form C |
| Alarm connector | Dual 20 panels: 0.045" square pin
Dual 10 panel: Screw terminals, #6-32 |
| Relay contact ratings | 0.6A at 48 VDC; 1A at 120 VAC |
| |
| Agency compliance | 06004-01 and 06004-11: NEBS 3, UL, CE
06020-01 NEBS 3, CE
009-2448-1001: UL, CE
|
| |
|